Cisco Physical Access Gateway Manual de usuario Pagina 55

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 114
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 54
© 2010 Cisco and/or its affiliates. All rights reserved.
Cisco ConfidentialPresentation_ID
55
What is a supervised input?
An unsupervised input has 2 states, active or inactive.
Supervised input has 4 states, active, inactive, short, and open.
Why do I care? What if a wire is cut or shorted between the module input
and a normally open device. The server could not determine this and the
device would remain in inactive state even when the switch is closed!
How do I make the device/input supervised?
Use 2 1K resistors in the circuit. In the inactive state, the circuit measures
2000 ohms, in the active state, the circuit measures 1000 ohms, short state
would measure 0 ohms, and open state would measure infinite ohms. Now I
can tell if a wire is cut or shorted
OHMs State Door
State
Error
Posted?
Input
Trusted?
2000 Inactive Closed No Yes
1000 Active Open No Yes
Zero Short ????? Yes No
Infinite Open ????? Yes No
Example used: Door Sensor
Vista de pagina 54
1 2 ... 50 51 52 53 54 55 56 57 58 59 60 ... 113 114

Comentarios a estos manuales

Sin comentarios