14
Note For installations compliant with the National Electric Code, AWG 14 (2.0 mm
2
) wire is required for DC input and
safety ground wire.
Wiring Procedure for DC Input
To connect the router to a DC power source, perform the following steps:
Step 1 Remove power from the DC circuit. To ensure that power is removed from the DC circuit, locate the circuit breaker
for the DC circuit, switch the circuit breaker to the OFF position, and tape the circuit-breaker switch in the OFF
position.
Warning
Before performing any of the following procedures, ensure that power is removed from the DC circuit.
Statement 1003
Tip Secure all power cabling when installing this unit to avoid disturbing field-wiring connections.
Step 2 Strip the wires 3/16 inch to 1/4 inch (5 mm to 7 mm).
Step 3 Remove the plastic cover from the terminal block. Save it for reinstallation after you finish wiring.
Step 4 Connect the wires to the terminal block, starting with the safety ground wire. Insert each wire into the appropriate
terminal as shown in Figure 8. To avoid interference with the on/off switch, insert the wires from below. Tighten the
terminal screws to 8.0 ± 0.5 in-lb (0.9 ± 0.05 N-m).
Warning
The illustration shows the DC power supply terminal block. Wire the DC power supply as illustrated. The proper
wiring sequence is ground to ground, positive to positive, and negative to negative. The ground wire should
always be connected first and disconnected last. Statement 239
Warning
An exposed wire lead from a DC-input power source can conduct harmful levels of electricity. Be sure that no
exposed portion of the DC-input power source wire extends from the terminal block plug. Statement 122
Caution Do not overtorque the terminal block contact screws. Recommended torque is 8.0 ± 0.5 in-lb (0.90 ± 0.05 N-m).
Table 2 DC Wiring Requirements for Cisco 3725 Routers
DC Power Source DC Input
DC Input
Wire Size
1
1. See the note above this table for National Electric Code wire size requirements.
Safety Ground
Wire Size
Overcurrent
Protection
Nominal 24/48 VDC
2
2. The input voltage tolerance limits for DC power are 18 and 72 VDC.
24–36 VDC, 9 A, positive or negative,
single source or dual sources
AWG 18
(1.0 mm
2
)
AWG 14
(2.0 mm
2
)
15 A maximum
36–60 VDC, 4 A, positive or negative,
single source or dual sources
AWG 18
(1.0 mm
2
)
AWG 14
(2.0 mm
2
)
15 A maximum