There is no change in the
module status because the
power capability is
unchanged.
•
Power supply is removed
with combined mode
enabled (redundancy
disabled).
System log and syslog
messages are generated.
•
System power is decreased
to the power capability of
one supply.
•
If there is not enough power
for all previously
powered−up modules, some
modules are powered down
and marked as power−deny
in the show module
command output status
field.
•
System is booted with
power supplies of different
wattage, or different types
are installed and
redundancy is enabled or
combined enabled.
System log and syslog
messages are generated.
•
System power is equal to
the first recognized power
supply.
•
The power supply
recognized second is kept
in err−disabled mode.
•
System is booted with
power supplies of equal
wattage and type installed
in combined more
(redundancy disabled).
System log and syslog
messages are generated.
•
System power is not the
sum of two power supplies.
It is P+ (P * ratio). Refer to
the Available Power for
Catalyst 4500 Series
Switches Power Supplies
section of the product
documentation for more
information.
•
The system powers−up as
many modules as the
combined capacity allows.
•
Configuration
The default power supply management mode is to use redundant mode. Issue this command to change the
mode to combined:
Switch (config)#power redundancy−mode combined
Issue this command to change the mode to redundant: