Cisco WS-C3550-24-FX-SMI - Catalyst 3550 100BASE-FX Switch Guía de instalación Pagina 79

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 150
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 78
2-33
Catalyst 3550 Multilayer Switch Hardware Installation Guide
78-11358-03
Chapter 2 Installing and Starting the Switch
Connecting to DC Power
Figure 2-32 Completed Wiring of Terminal Block Plug
Step 7
Insert the terminal block plug in the terminal block header on the switch rear
panel, as shown in Figure 2-33.
Caution Secure the wires coming in from the terminal block so that they cannot be
disturbed by casual contact. For example, use tie wraps to secure the wires to the
rack.
Figure 2-33 Inserting the Terminal Block in the Block Header
60534
Return
Negative
Return
Negative
Feed A
Feed B
CONSOLE
36 - 72V
1 - 0.5A
A
B
65805
Tie wrap
Vista de pagina 78
1 2 ... 74 75 76 77 78 79 80 81 82 83 84 ... 149 150

Comentarios a estos manuales

Sin comentarios